TM 9-4940-568-34
7-80
7-10. GENERATOR REPAIR (CONT).
(3)
Disconnect lead (6) from PMG stator (7).
NOTE
Note position of PMG stator
before removal.
(4)
Remove four spacers (8), lockwashers (9),
clamps (10) and PMG stator (7) from
generator (3). Discard lockwashers.
NOTE
Use wooden block to hold fan in
position.
(5)
Remove PMG mount screw (11),
lockwasher (12) and PMG rotor (13) from
generator (3). Discard lockwasher.
7
8
9
10
11
12
13
6
3
3