1
2
3
4
5
7
8
9
10
11
12
13
3
6
3
13
TM 9-4940-568-34
7-83/(7-84 blank)
(9)
Install PMG rotor (13), lockwasher (12) and
PMG mount screw (11).
(10)
Tighten PMG mount screw (11) to 40 lb-ft
(19 N.m).
NOTE
Position PMG stator as noted
during removal.
(11)
Install PMG stator (7) on PMG rotor (13).
(12)
Install four clamps (10), lockwashers (9)
and four spacers (8) on PMG stator (7) and
generator (3).
(13)
Tighten spacers (8) to 7 lb-ft (3 N.m)
(14)
Install lead (6) to PMG stator (7).
(15)
Install four screws (4) and end bell cover
(5) on generator (3).
(16)
Install eight screws (1) and three drive
disks (2) on generator (3).
(17)
Tighten screws (1) to 95 lb-ft (43 N.m).
c.
Follow-On Maintenance:
Install generator set, (Para 5-3).
Connect batteries, (TM 9-4940-568-10).
Start generator and check for proper operation,
(TM 9-4940-568-10).
END OF TASK