TM 9-4940-568-34
5-14
5-3. GENERATOR SET REPLACEMENT (CONT).
59
8
55
53
52
54
60
57
58
56
8
(24)
Remove two self-tapping screws (52) and brackets (53) from generator set enclosure (8). Discard
self-tapping screws.
(25)
Remove four small rubber covers (54) and four large rubber covers (55) from generator set enclosure to
expose screws (56).
(26)
Remove four screws (56), washers (57) and washers (58) from generator set enclosure (8) and flatrack
(59).
Generator set enclosure weighs approximately 2450 lbs (1111 kg). Attach suitable
lifting device to prevent possible injury to personnel.
(27)
With the aid of assistants, position S-hooks (60) and attach lifting device to generator set enclosure (8).
(28)
With the aid of assistants, raise generator set enclosure (8) approximately 20 in. (508 mm) and ensure
load is balanced.
(29)
With the aid of assistants, position generator set enclosure (8) on wooden blocks.
(30)
Remove lifting device and four S-hooks (60) from generator set enclosure (8).