Table 1. 1295 Apron Float Indicator Diagnostic Codes Continued.
083
CID FMI
TEST OR INSPECTION
CORRECTIVE ACTION
NOTE
1295-05 Apron Float Lamp
Current Below Normal
Always inspect harness connectors that are involved in the circuit. Poor
connections can often be the cause of a problem in an electrical circuit.
Verify that all connections in the circuit are clean and secure and that all
connections are in good condition. If a problem with the connection is
found, correct the problem and verify that this malfunction or diagnostic
code is active before performing this procedure.
Perform open or short-circuit test at each harness connection to identify
the correct harness to replace.
Tag all wiring harnesses to aid in installation.
Perform this test only if condition is active.
DIAGNOSTIC CODE SET CONDITION
Transmission/Chassis ECM Detects Abnormally Low Current on Apron Float
Lamp Circuit R745 During Lamp Test or Apron Float Operation.
POSSIBLE CAUSE
Apron Float LED Open.
Transmission/Chassis ECM.
0083-5