SECTION III. OPERATION UNDER USUAL CONDITIONS
2-1.
ASSEMBLY AND PREPARATION FOR USE
2-1.1.
Installation.
Step 1.
Ensure equipment power is not connected.
Step 2.
Remove Grounding Kit from tool bag.
Step 3.
Attach terminal lug to grounding stud on Power Entrance Panel of equipment being grounded.
Step 4.
Lay cable around the perimeter of equipment, distributing stakes evenly and creating an open-ended
("U" shaped) pattern with no overlapping of cables.
Step 5.
Begin with the stake closest to the grounding stud. Pull cable taut. Twist stake 30° to 45°. Drive stake
until top is flush with ground. Continue until stakes are all driven into ground.
Step 6.
Attach jumper cables. Connect one from front bumper of vehicle to center of cable; connect second from
rear bumper of vehicle to end of grounding cable.
2-1.2.
Removal
Step 1.
Disconnect equipment power and discharge supply capacitors.
Step 2.
Remove jumper cables.
2-4