• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
POWER DISTRIBUTION UNIT - Continued
POWER DISTRIBUTION UNIT - Continued

Technical Manual For Power Distribution Unit
Page Navigation
  27    28    29    30    31  32  33    34    35    36    37  
img
. . .
TM 3-4240-302-30&P-5
2-7. POWER DISTRIBUTION UNIT (CONT).
LOCATION
ITEM
ACTION
REMOVAL
Panel
208 V indicator light
1.
Unscrew lens (1), and pull out lamp (2).
2.
Unscrew knurled ring (3), and remove
indicator light (4) and washer (5).
3.
Remove insulation, and unsolder and tag
connections from indicator light (4).
INSTALLATION
1.
Place insulation sleeving (item 1, app C) over
wire leads.
2.
Solder wire leads to 208 V indicator light.
Refer to wiring diagram (p. 2-39).
3.
Place insulation sleeving (item 1, app C) over
connection and shrink.
4.
Insert 208 V indicator light (4) in panel, and
secure to panel (6) with knurled ring (3) and
washer (5).
5.
Install lamp (2) in lens (1).
6.
Screw lens (1) in indicator light.
2-30


Privacy Statement