WARNING
(p)
(q)
(r)
(s)
TM 9-6230-210-13&P
Place grounding clamp (8) over rod and tighten (finger tight only) to rod, approximately 6-inches(15 cm)
down from end of rod. Then replace coupling.
Attach grounding wire (9) to damp with wire between rod an screw of damp, and tighten screw.
Attach grounding lug located at other end of grounding wire to Floodlight Set.
Replace hammer is storage rack and install safety pin and spring dip.
Use extreme care when hooking up to external power. HIGH VOLTAGE may be en-
countered.
l. Instructions for Wiring the Floodlight Set to Operate On External Power.
(1)
(2)
(3)
(4)
(5)
(6)
Disconnect and remove the control box/generator set cable.
Connect jumper wire (No. 10 AWG) from left circuit breaker terminal to right circuit breaker terminal.
NOTE
Wire should be long enough to go around circuit breaker rather than across the
top.
Using a 2-conductor No. 10, 100-Ft. (30.5 m) cable, insert one end into control box. Hole is provided on side
of control box below the duplex receptacle.
Connect black wire to right circuit breaker terminal.
Connect white wire to terminal on extreme left side of control box. (Same terminal used for white wire in
generator set cable).
Other end of cable is connected to external power source.
2.8
OPERATING PROCEDURES.
a. Floodlight Set Operation.
LEGEND
1 SPRING CLIP
2 CRADLE CLEAT
3 CRADLE
4 TOWER
(1) Remove spring dip (1) from tower cradle cleat (2).
2-19