POWER DISTRIBUTION UNIT - Continued
POWER DISTRIBUTION UNIT - Continued

Technical Manual For Power Distribution Unit
Page Navigation
  34    35    36    37    38  39  40    41    42    43    44  
img
. .
TM 3-4240-302-30&P-5
LOCATION
ITEM
ACTION
REMOVAL
Panel
DUST FAN circuit
1.
Remove six screws (1), washers (2), and wires
breaker CB4
(3) from circuit breaker CB4 (4). Tag wires.
2.
Unsolder and tag wires from A3 and A4
contacts on circuit breaker CB4 (4).
3.
Unscrew boot (5), and remove circuit breaker
CB4 (4) from panel (6).
INSTALLATION
1.
Insert circuit breaker (4) in panel (6), and
secure with boot (5).
2.
Solder wires to A3 and A4 contacts of circuit
breaker. Refer to wiring diagram (p. 2-39).
3.
Install wires (3) on six electrical terminals using
six screws (1) and washers (2). Refer to wiring
diagram (p. 2-39).
2-37