2-11. PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS)
TABLES (CONT).
Table 2-1. Operators Level Preventive Maintenance Checks and Services (Before) (CONT).
Item
No.
Interval
Item to
Check/
Service
Procedure
Not Fully Mission
Capable If:
NOTE
Remove access panels as necessary for checks
and services.
16
Before
Generator/
Engine Set
(a) Check generator engine set housing for
loose or missing parts and hardware. Check
access panel doors and control panel door (1)
for obvious damage and any loose or missing
hardware or seals.
(b) Visually check for evidence of leaks.
(c) Check engine oil level (2). Check air filter
restriction indicator (3).
Class II fuel leak and/or
Class III oil leak is
evident.
(d) Check generator/engine set for any broken,
missing or damaged hardware.
(e) Check surge tank coolant level (4).